8
Technical Manual
Kingspan SHE Control Panel TRZ Plus
2A and TRZ Plus Comfort
12/24999513
Description of Function
Automatic Ventilation Control
If activated (see start up procedure), the windows are
closing automatically after xx min (10 min factory-
made), in case of mains or battery failure, the windows
close immediately.
See also page 25, DIP-Switch 12.
Mains or battery failure
- Automatic closing of the flaps
- Ventilation function locked, SHE function active
Note:
These are standard features for mains or
battery failure,Special function: see DIP switch
function 3 + 10
Extraction Limit (by operating time)
See note on page 62, switch DIP-Switch 6 to ON.
Teaching
Close the windows. Earliest start of the learning mode
after 30 seconds. Press the switches “Open” and “Closed”
(STOP) at the vent switch as long as the display “Open” is
flashing fast. Open the motor with the switch “Open” up
to the position required within the next 10 sec. and stop
the motor in this position by releasing the switch “Open”.
If no other switch is pressed within the next 10 sec. the
learning phase is finished.
To Deactivate
See note on page 20, switch DIP-Switch 6 to OFF.
Note:
If the vent switch has no Open-display or
there is no ventilation button in the door of the
TRZ-Plus Comfort the stroke limit setting must be
made through the optional service port software.
Note:
In case of mains or battery failure or SHE
activation the function is out of order. In case
of mains or battery failure, the windows close
immediately.
LED Display
In the SHE control panel and SHE manual call points.
The green LED display
OK
- operating OK - is shining. It
goes out in case of:
- mains or battery failure
- malfunction of the line monitoring of the connected
drives, automatic detectors or SHE manual call points.
The yellow LED display
- malfunction - is flashing in
case of: malfunction, cable connection defective, mains
and/or battery failure.
Caution:
If any malfunction is indicated the
malfunction has to be eliminated immediately.
The perfect function of the system is no longer
guaranteed.
The red LED display
- SHE activation - is shining in
case of: manual or automatic SHE activation.
Closing with Wind/Rain Detector
If a wind/rain detector or a rain sensor is connected, the
windows close automatically in case of beginning winds
and/or rainfall, “Ventilation Open” display flashes, vent
switch out of order. The windows close immediately in
case of power or battery failure.
Note:
The ventilation function is out of order or
locked in case of power or battery failure or SHE
activation in order to save battery power.