7
Technical Manual
Kingspan SHE Control Panel TRZ Plus
2A and TRZ Plus Comfort
12/24999513
Description of Function
Universally
Smoke-Heat-Extraction- (SHE) and Ventilation control panel
for 24V DC drives with a maximum Current draw of 2A.
To open and close flaps, windows, skylight domes and for
smoke extraction and daily ventilation. SHE and ventilation
functions via manual and automated control devices.
Self-monitoring system with malfunction indication via LED
flashlight. Integrated power back up for 72h according to
DIN EN 12101-10 and VdS 2593. SHE-functions according to
prEN 12101-9 and VdS 2581. Extended functions for use in
elevator shafts according to VdS guideline 2895. Electrical
safety with TÜV approval. Installed within plastic or metal
housing available for surface or in flush mounted version with
additional flush mounting set.
Manual activation in case of fire/smoke/
alarm
Smoke heat extraction / opening windows
Press the red Open switch
at a SHE manual call point,
the windows open completely, the red LED display
-
SHE activated - is shining at all SHE manual call points, the
ventilation function is out of order.
Smoke heat extraction / closing windows
Press the switch “Closed”
at a SHE manual call point, the
windows are closing, the red LED display
- SHE activated
- goes out at all SHE manual call points, the ventilation
function is working again.
Note:
There is no Reset of the connected and
activated automatic detectors!
Automatic activation in case of fire/smoke/
alarm
(If automatic detectors are connected only)
Smoke heat extraction / opening windows
Smoke reaches the automatic detectors, the windows are
opened completely, the red display in the automatic detector
is shining, the red LED display
- SHE activated - is shining
at all SHE manual call points, the ventilation function is out
of order.
Smoke heat extraction / closing windows
Press the switch “Closed”
at a SHE manual call point, the
windows are closing, the red LED display
- SHE activated
- goes out at all SHE manual call points, the yellow LED
display
- malfunction - flashes.
Note:
there is no Reset of the connected and
activated automatic detectors!
Reset of automatic detectors
Set the automatic detectors free from smoke by blowing out
or replace them in case of heavy soiling.
Press the Reset switch on the basic circuit control board of
the control panel, the windows are closing, the red display
in the automatic detectors goes out, the red LED display
- SHE activated - goes out at all SHE manual call points,
the yellow LED display
- malfunction - goes out, the
ventilation function is working again.
Daily ventilation
(If vent switches are connected only respectively via
operating element of the TRZ Plus Comfort)
Opening windows
Press the switch “Open” at the vent switch, the windows
open completely. (Interruption of the opening by pressing
both switches together (Open and Closed) = STOP or by Stop
switch depending on vent switch).
Closing windows
Press the switch “Closed” at the vent switch, the windows
close completely. (Interruption of the opening by pressing
both switches together (Open and Closed) = STOP or by
Stop switch depending on vent switch). In case of mains or
battery failure, the windows close immediately.