BOP HIPWR 080709
3-27
3.3.9.5
VIEWING STORED WAVEFORMS
After observing the precautions of PAR. 3.3.9.1, press
@
from the power-up screen to access
the Saved Waveforms screen (Figure 3-9). Use
Y
or
U
or the encoder to highlight the name of
a previously saved waveform, then press
!
to view the Waveform Settings screen (see Figure
3-10). The lower half of the LCD shows a representation of the programmed waveform. The let-
ters along the vertical axis of the graph at the lower left side indicate whether the waveform is
programmed to operate in voltage or current mode. The message at the upper right indicates
the actual mode of the power supply while the waveform is being executed. The upper half pres-
ents the waveform name, positive and negative protection settings, the repetition count, fol-
lowed by a listing of segments. The type (square, sine, etc.), frequency, p-p amplitude, and
TABLE 3-9. SINE, TRIANGLE AND RAMP WAVEFORM FREQUENCY VS. POINTS
Frequency
(See Notes 1, 2, and 3)
Total Points
Frequency
(See Notes 1, 2, and 3)
Total Points
From
To
From
To
0.01Hz
2.7Hz
3840
55.5Hz
66.5Hz
160
2.71Hz
3.6Hz
2880
66.6Hz
88.7Hz
120
3.71Hz
5.5Hz
1920
88.8Hz
118.3Hz
90
5.6Hz
8.3Hz
1280
118.4Hz
147.9Hz
72
8.4Hz
11.0Hz
960
148Hz
177.4Hz
60
11.1Hz
14.7Hz
720
177.5Hz
221.8Hz
48
14.8Hz
22.1Hz
480
221.9Hz
295.8Hz
36
22.2Hz
33.2Hz
320
295.81Hz
354.9Hz
30
33.3Hz
44.3Hz
240
355.9Hz
443.7Hz
24 (See Note 2)
44.4Hz
55.4Hz
192
443.8z
532Hz
20 (See Note 3)
NOTES: 1. As the frequency varies within the range, the time interval per point varies proportionately.
2. Sine and Triangle segments can not exceed 443Hz.
3. Ramp segments can not exceed 532Hz.
TABLE 3-10. SQUARE WAVEFORM FREQUENCY VS. POINTS
Frequency
(See Note 1)
Total Points
Frequency
(See Notes 1)
Total Points
From
To
From
To
0.02Hz
1.8Hz
3840
43.51Hz
58.0Hz
120
1.81Hz
2.7Hz
2880
58.01Hz
72.5Hz
90
2.71Hz
4.0Hz
1920
72.51Hz
87.0Hz
72
4.01
5.4Hz
1280
87.01Hz
108.7Hz
60
5.41
7.2Hz
960
108.71Hz
145.0Hz
48
7.21Hz
10.8Hz
720
145.2.9Hz
174.0Hz
36
10.81
16.3Hz
480
174.1Hz
217.5Hz
30
16.31Hz
21.7Hz
320
217.6Hz
261.0Hz
24
21.71Hz
27.1Hz
240
261.1Hz
435.0Hz
20
27.11Hz
32.6Hz
192
435Hz
652.5Hz
12
55.5Hz
66.5Hz
160
653
1000
10
NOTE: 1. As the frequency varies within the range, the time interval per point varies proportionately.
Содержание BOP 1000W
Страница 2: ......
Страница 10: ......
Страница 20: ......
Страница 31: ......
Страница 32: ......
Страница 36: ......
Страница 50: ...FIGURE 2 2 LOAD CONNECTIONS LOCAL SENSING...
Страница 53: ......
Страница 54: ......
Страница 55: ......
Страница 56: ......
Страница 57: ......
Страница 61: ...FIGURE 2 11 POWER ON DEFAULT SCREEN FOR SLAVE UNIT 2 8 4 OPERATING INSTRUCTIONS FOR MULTIPLE UNIT COMBINATIONS...
Страница 63: ...080709 C 25 FIGURE 2 12 3 X 2 3 SERIES X 2 PARALLEL CONFIGURA TION LOCAL SENSING TYPICAL 2 25 2 26 Blank 24 25...
Страница 64: ......
Страница 68: ...FIGURE 3 3 POWER UP SCREEN SHOWING GRAPHIC METERS VOLTAGE 0000 0...
Страница 125: ......
Страница 128: ......