2-24
BOP HIPWR 080709
2.8.5
RESTORING A UNIT TO STANDALONE OPERATION
1. Turn off power to the master.
2. Turn off power to the slave(s).
3. Turn on power to the unit to be restored to standalone operation.
4. From the power-up screen press
%
to enter the General Setup Menu. Highlight
Series/
Parallel
and press
!
to view the Multiple Units menu (see Table 2-12). When prompted,
enter ADMIN2 password (see PAR. 3.2.4.4) before continuing.
5. Press
@
to return to factory defaults. This configures the unit as a standalone unit.
6. Press
$
to save for power-up.
7. Turn off power to the unit, then turn power on. The unit will power up as a standalone unit.
2.8.6
CHANGING MULTIPLE UNIT CONFIGURATIONS
To change a unit from series, parallel, Master 2X2 or Master 3X2 operation to a different config-
uration, first set the unit to Standalone by referring to PAR. 2.8.5, then refer to PAR. 2.8.3 and
configure as desired.
Содержание BOP 1000W
Страница 2: ......
Страница 10: ......
Страница 20: ......
Страница 31: ......
Страница 32: ......
Страница 36: ......
Страница 50: ...FIGURE 2 2 LOAD CONNECTIONS LOCAL SENSING...
Страница 53: ......
Страница 54: ......
Страница 55: ......
Страница 56: ......
Страница 57: ......
Страница 61: ...FIGURE 2 11 POWER ON DEFAULT SCREEN FOR SLAVE UNIT 2 8 4 OPERATING INSTRUCTIONS FOR MULTIPLE UNIT COMBINATIONS...
Страница 63: ...080709 C 25 FIGURE 2 12 3 X 2 3 SERIES X 2 PARALLEL CONFIGURA TION LOCAL SENSING TYPICAL 2 25 2 26 Blank 24 25...
Страница 64: ......
Страница 68: ...FIGURE 3 3 POWER UP SCREEN SHOWING GRAPHIC METERS VOLTAGE 0000 0...
Страница 125: ......
Страница 128: ......