BOP HIPWR 080709
2-19
FIGURE 2-8. TYPICAL MASTER/SLAVE PROTECTION INTERCONNECTIONS
Upon startup, PAR/SER PROT IN PORT pin 8 of the master goes low, and stays low until all
slaves are powered up. Normal power up of a unit causes the transistor connecting PAR/SER
PROT IN PORT pin 2 and PAR/SER PROT OUT PORT pin 2 to conduct. The transistors of all
units are connected in series, effectively shorting out all the shutdown diodes (the shutdown
diodes of all units are also connected in series) connecting PAR/SER PROT IN PORT pin 1 and
PAR/SER PROT OUT PORT pin 1. After all the units are powered up and operating normally,
the low at PAR/SER PROT IN PORT pin 8 changes to high, but the conducting transistors keep
the voltage at pin 8 low and the diodes are cut off. If a fault occurs, the transistor between PAR/
SER PROT IN PORT pin 2 and PAR/SER PROT OUT PORT pin 2 of the defective unit is cut off,
allowing current to flow through the shutdown diodes. This develops internal shutdown signals
that shut down all units.
2.8.3
CONFIGURING PARALLEL, SERIES, 2 X 2 OR 3 X 2 COMBINATIONS
NOTE: To power down the combination, first press the
STANDBY
key on the master to dis-
able the output, then turn off the slave(s) followed by the master.
1. To configure a unit to be designated as a slave proceed as follows:
a. Turn on power only to the unit to be designated as a slave.
b. From the power-up screen press
%
to enter the General Setup Menu. Highlight Series/
Parallel and press
!
to view the Multiple Units menu (see Table 2-12). If required, enter
password (see PAR. 3.2.4.4) before continuing.
Содержание BOP 1000W
Страница 2: ......
Страница 10: ......
Страница 20: ......
Страница 31: ......
Страница 32: ......
Страница 36: ......
Страница 50: ...FIGURE 2 2 LOAD CONNECTIONS LOCAL SENSING...
Страница 53: ......
Страница 54: ......
Страница 55: ......
Страница 56: ......
Страница 57: ......
Страница 61: ...FIGURE 2 11 POWER ON DEFAULT SCREEN FOR SLAVE UNIT 2 8 4 OPERATING INSTRUCTIONS FOR MULTIPLE UNIT COMBINATIONS...
Страница 63: ...080709 C 25 FIGURE 2 12 3 X 2 3 SERIES X 2 PARALLEL CONFIGURA TION LOCAL SENSING TYPICAL 2 25 2 26 Blank 24 25...
Страница 64: ......
Страница 68: ...FIGURE 3 3 POWER UP SCREEN SHOWING GRAPHIC METERS VOLTAGE 0000 0...
Страница 125: ......
Страница 128: ......