Basic operation instructions
-89-
Function
code
Name
Detailed parameter description
Default
value
DeviceNet communication
10: Set via Ethernet communication
11: Set via high speed pulse HDIB
12: Set via pulse string AB
13: Set via EtherCAT/PROFINET
communication
14: Set via PLC card
15: Reserved
P00.08
Reference object of B
frequency command
0: Max. output frequency
1: A frequency command
0
P00.09
Combination mode of setting
source
0: A
1: B
2: (A+B)
3: (A-B)
4: Max (A, B)
5: Min (A, B)
0
P05.01–
P05.06
Function of multi-function
digital input terminal (S1–S4,
HDIA, HDIB)
10: Frequency increase (UP)
11: Frequency decrease (DOWN)
12: Clear frequency increase/decrease
setting
13: Switch-over between setting A and
setting B
14: Switch-over between combination
setting and setting A
15: Switch-over between combination
setting and setting B
/
P08.42
Reserved variables
/
/
P08.43
Reserved variables
/
/
P08.44
UP/DOWN terminal control
0x000–0x221
Ones: Frequency enabling selection
0: Setting through the UP/DOWN
terminal is valid
1: Setting through the UP/DOWN
terminal is invalid
Tens: Frequency control selection
0: Valid only when P00.06=0 or P00.07=0
1: Valid for all frequency modes
2: Invalid for multi-step speed when
0x000