Basic operation instructions
-120-
Function
code
Name
Detailed parameter description
Default
value
P08.15
Amplitude of wobbling
frequency
0.0–100.0% (relative to set frequency)
0.0%
P08.16
Amplitude of jump frequency
0.0–50.0% (relative to amplitude of
wobbling frequency)
0.0%
P08.17
Wobbling frequency rise
time
0.1–3600.0s
5.0s
P08.18
Wobbling frequency fall time 0.1–3600.0s
5.0s
5.5.17 Local encoder input
The GD350-UL series VFD supports pulse count function by inputting the count pulse from HDI
high-speed pulse port. When the actual count value is no less than the set value, digital output
terminal will output count-value-reached pulse signal, and the corresponding count value will be
zeroed out.
Function
code
Name
Detailed parameter description
Default
value
P05.00
HDI input type
0x00–0x11
Ones: HDIA input type
0: HDIA is high-speed pulse input
1: HDIA is digital input
Tens: HDIB input type
0: HDIB is high-speed pulse input
1: HDIB is digital input
0x00
P05.38
HDIA high-speed pulse input
function
0: Set input via frequency
1: Reserved
2: Input via encoder, used in combination
with HDIB
0
P05.44
HDIB high-speed pulse input
function selection
0: Set input via frequency
1: Reserved
2: Input via encoder, used in combination
with HDIA
0
P20.15
Speed measurement mode
0: PG card
1: local; realized by HDIA and HDIB;
supports incremental 24V encoder only
0
P18.00
Actual frequency of encoder -999.9–3276.7Hz
0.0Hz
5.5.18 Commissioning procedures for position control and spindle positioning function
1. Commissioning procedures for closed-loop vector control of asynchronous motor
Step 1: Restore to default value via keypad
Step 2: Set P00.03, P00.04 and P02 group motor nameplate parameters