Goodrive350-UL Series VFD
Function parameter list
-188-
Function
code
Name
Detailed parameter description
Default
value
Modi
fy
P10.11
Running time of
4
th
step
P10.02
P10.04
P10.06
P10.32
P10.30
P10.28
Deceleration time
(two sections)
Acceleration time
(two sections)
P10.03
P10.05
P10.07
P10.31
P10.33
When selecting multi-step speed running, the
multi-step speed is within the range of -fmax–fmax,
and it can be set continuously. The start/stop of
multi-step stop is also determined by P00.01.
Goodrive350-UL series VFD can set 16-step speed,
which are set by combined codes of multi-step
terminals 1–4 (set by S terminal, correspond to
function code P05.01–P05.06) and correspond to
multi-step speed 0 to multi-step speed 15.
Output frequency
t
t
t
t
t
terminal 1
terminal 2
terminal 3
terminal 4
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
When terminal 1, terminal 2, terminal 3 and terminal
4 are OFF, the frequency input mode is set by
P00.06 or P00.07. When terminal 1, terminal 2,
terminal 3 and terminal 4 are not all OFF, the
frequency set by multi-step speed will prevail, and
the priority of multi-step setting is higher than that of
the keypad, analog, high-speed pulse, PID, and
communication settings.
The relation between terminal 1, terminal 2, terminal
3 and terminal 4 are shown in the table below.
0.0s(min)
○
P10.12 Multi-step speed 5
0.0%
○
P10.13
Running time of
5
th
step
0.0s(min)
○
P10.14 Multi-step speed 6
0.0%
○
P10.15
Running time of
6
th
step
0.0s(min)
○
P10.16 Multi-step speed 7
0.0%
○
P10.17
Running time of
7
th
step
0.0s(min)
○
P10.18 Multi-step speed 8
0.0%
○
P10.19
Running time of
8
th
step
0.0s(min)
○
P10.20 Multi-step speed 9
0.0%
○
P10.21
Running time of
9
th
step
0.0s(min)
○
P10.22
Multi-step speed
10
0.0%
○
P10.23
Running time of
10
th
step
0.0s(min)
○
P10.24
Multi-step speed
11
0.0%
○
P10.25
Running time of
11
th
step
0.0s(min)
○
P10.26
Multi-step speed
12
0.0%
○
P10.27
Running time of
12
th
step
0.0s(min)
○
P10.28
Multi-step speed
13
0.0%
○
P10.29
Running time of
13
th
step
0.0s(min)
○
P10.30
Multi-step speed
14
0.0%
○
P10.31
Running time of
14
th
step
0.0s(min)
○
Содержание GD350-004G-2-UL