Goodrive350-UL Series VFD
Function parameter list
-134-
Function
code
Name
Detailed parameter description
Default
value
Modi
fy
acceleration and deceleration time, which can be
selected via multi-function digital input terminals
(P05 group). The acceleration/deceleration time of
the VFD is the first group by default.
Setting range of P00.11 and P00.12: 0.0–3600.0s
P00.13 Running direction
0: Run in default direction
1: Run in reverse direction
2: Reverse running is prohibited
0
○
P00.14
Carrier frequency
setting
Carrier
frequency
Electro magnetic
noise
Noise and leakage
current
Cooling
level
High
Low
High
Low
High
Low
1kHz
10kHz
15kHz
The relation between the model and carrier
frequency is shown below.
Model
Factory value
of carrier
frequency
220V
0.75–55kW
2kHz
460V
1.5–11kW
8kHz
15–55kW
4kHz
75–500kW
2kHz
575V
22–55kW
4kHz
75–110kW
2kHz
Advantages of high carrier frequency are as follows:
ideal current waveform, few current harmonics and
small motor noise.
Disadvantages of high carrier frequency are as
follows: growing switch consumption, enlarged
temperature rise, impacted output capacity; under
high carrier frequency, the VFD needs to be derated
for use, meanwhile, the leakage current will
increase,
which
increases
electromagnetic
interference to the surroundings.
While low carrier frequency is the contrary. Low
carrier frequency will cause unstable operation at
Depend
on model
○