Goodrive350-UL Series VFD
Function parameter list
-185-
Function
code
Name
Detailed parameter description
Default
value
Modi
fy
P09.07
Sampling cycle
(T)
It means the sampling cycle of feedback. The
regulator operates once during each sampling cycle.
The larger the sampling cycle, the slower the
response.
Setting range: 0.001–10.000s
0.001s
○
P09.08
Limit of PID
control deviation
It is the max. allowable deviation of PID system
output value relative to closed-loop reference value.
Within this limit, PID regulator stops regulation. Set
this function code properly to regulate the precision
and stability of PID system.
Setting range: 0.0–100.0%
Reference
Deviation
limit
Feedback
Output
frequency f
Time t
Time t
0.0%
○
P09.09
Upper limit value
of PID output
These two function codes are used to set the
upper/lower limit value of PID regulator.
100.0% corresponds to Max. output frequency
(P00.03) or max. voltage (P04.31)
Setting range of P09.09: P09.10–100.0%
Setting range of P09.10: -100.0%–P09.09
100.0%
○
P09.10
Lower limit value
of PID output
0.0%
○
P09.11
Feedback offline
detection value
Set PID feedback offline detection value, when the
detection value is no more than the feedback offline
detection value, and the duration exceeds the value
set in P09.12, the VFD will report "PID feedback
offline fault", and keypad displays PIDE.
T
Output frequency
t1
t2
P09.11
t1
<
T2, so the VFD
continues running
t2=P09.12
Running
Fault output PIDE
PIDE
0.0%
○
P09.12
Feedback offline
detection time
1.0s
○