Goodrive350-UL Series VFD
Function parameter list
-205-
Function
code
Name
Detailed parameter description
Default
value
Modi
fy
0000–03F
Corresponds to HDIB, HDIA, S4, S3, S2 and S1
respectively
P17.13
Digital output
terminal state
Display current digital output terminal state of the
VFD.
0000–000F
Corresponds to R02, RO1, HDO and Y1 respectively
0
●
P17.14
Digital
adjustment
variable
Display the regulating variable by UP/DOWN
terminals of the VFD.
Range: 0.00Hz–P00.03
0.00Hz
●
P17.15
Torque reference
value
Relative to percentage of the rated torque of current
motor, display torque reference.
Range: -300.0%–300.0% (rated motor current)
0.0%
●
P17.16
Linear speed 0–65535
0
●
P17.17
Reserved
variables
0–65535
0
●
P17.18
Count value
0–65535
0
●
P17.19 AI1 input voltage
Display input signal of AI 1
Range: 0.00–10.00V
0.00V
●
P17.20 AI2 input voltage
Display input signal of AI2
Range: -10.00V–10.00V
0.00V
●
P17.21
HDIA input
frequency
Display input frequency of HDIA
Range: 0.000–50.000kHz
0.000
kHz
●
P17.22
HDIB input
frequency
Display input frequency of HDIB
Range: 0.000–50.000kHz
0.000
kHz
●
P17.23
PID reference
value
Display PID reference value
Range: -100.0–100.0%
0.0%
●
P17.24
PID feedback
value
Display PID feedback value
Range: -100.0–100.0%
0.0%
●
P17.25
Motor power
factor
Display the power factor of current motor.
Range: -1.00–1.00
1.00
●
P17.26
Current running
time
Display current running time of the VFD.
Range: 0–65535min
0m
●
P17.27
Simple PLC and
current step
number of
multi-step speed
Display simple PLC and current step number of
multi-step speed
Range: 0–15
0
●
P17.28
Motor ASR
Display the speed loop ASR controller output value
0.0%
●