Goodrive350-UL Series VFD
Basic operation instructions
-62-
Function
code
Name
Detailed parameter description
Default
value
1: Reserved
Tens place: Reserved
0: Reserved
1: Reserved
Hundreds place: ASR integral separation
enabling
0: Disabled
1: Enabled
Thousands place: Reserved
0: Reserved
1: Reserved
Range: 0x0000–0x1111
P03.36
ASR differential gain
0.00–10.00s
0.00s
P03.37
High-frequency ACR
proportional coefficient
In the closed-loop vector control mode
(P00.00=3), when the frequency is lower
than the ACR high-frequency switching
threshold (P03.39), the ACR PI parameters
are P03.09 and P03.10; and when the
frequency is higher than the ACR
high-frequency
switching
threshold
(P03.39), the ACR PI parameters are
P03.37 and P03.38.
Setting range of P03.37: 0–20000
Setting range of P03.38: 0–20000
Setting range of P03.39: 0.0–100.0% (in
relative to the maximum frequency)
1000
P03.38
High-frequency ACR
integral coefficient
1000
P03.39
ACR high-frequency
switching threshold
100.0%
P17.32
Flux linkage
0.0–200.0%
0.0%
5.5.4 SVPWM control mode
GD350-UL VFD also carries built-in SVPWM control function. SVPWM mode can be used in cases
where mediocre control precision is enough. In cases where a VFD needs to drive multiple motors, it
is also recommended to adopt SVPWM control mode.
GD350-UL VFD provides multiple kinds of V/F curve modes to meet different field needs. Users can
select corresponding V/F curve or set the V/F curve as needed.
Suggestions:
1.
For the load featuring constant moment, eg, conveyor belt which runs in straight line, as the
moment should be constant during the whole running process, it is recommended to adopt
straight-type V/F curve.