Goodrive350-UL Series VFD
Basic operation instructions
-118-
Function
code
Name
Detailed parameter description
Default
value
0: Continue integral control after the
frequency reaches upper/lower limit
1: Stop integral control after the
frequency reaches upper/lower limit
Tens:
0: The same with the main reference
direction
1: Contrary to the main reference
direction
Hundreds:
0: Limit as per the max. frequency
1: Limit as per A frequency
Thousands:
0: A+B frequency, acceleration
/deceleration of main reference A
frequency source buffering is invalid
1: A+B frequency, acceleration/
deceleration of main reference A
frequency source buffering is valid,
acceleration/deceleration is determined
by P08.04 (acceleration time 4).
P17.00
Set frequency
0.00Hz–P00.03 (Max. output frequency)
0.00Hz
P17.23
PID reference value
-100.0–100.0%
0.0%
P17.24
PID feedback value
-100.0–100.0%
0.0%
5.5.16 Run at wobbling frequency
Wobbling frequency is mainly applied in cases where transverse movement and winding functions are
needed like textile and chemical fiber industries. The typical working process is shown as below.