Goodrive350-UL Series VFD
Maintenance and hardware fault diagnosis
-262-
Storage time
Operation principle
charge it at 50% of the rated voltage for 30 minutes, at 75% for
another 30 minutes, and finally charge it at 100% of the rated voltage
for 30 minutes.
More than 3 years
Use a voltage controlled power supply to charge the VFD:
Charge the VFD at 25% of the rated voltage for 2 hours, and then
charge it at 50% of the rated voltage for 2 hours, at 75% for another 2
hours, and finally charge it at 100% of the rated voltage for 2 hours.
The method for using a voltage controlled power supply to charge the VFD is described as follows:
The selection of a voltage controlled power supply depends on the power supply of the VFD. For
VFDs with an incoming voltage of 1PH/3PH 230 V AC, you can use a 230 V AC/2 A voltage regulator.
Both 1PH and 3PH VFDs can be charged with a 1PH voltage controlled power supply (connect L+ to
R, and N to S or T). All the DC bus capacitors share one rectifier, and therefore they are all charged.
For VFDs of a high voltage class, ensure that the voltage requirement (for example, 460 V) is met
during charging. Capacitor changing requires little current, and therefore you can use a
small-capacity power supply (2 A is sufficient).
The method for using a resistor (incandescent lamp) to charge the drive is described as follows:
If you directly connect the drive device to a power supply to charge the DC bus capacitor, it needs to
be charged for a minimum of 60 minutes. The charging operation must be performed at a normal
indoor temperature without load, and you must connect a resistor in series mode in the 3PH circuit of
the power supply.
For a 460 V drive device, use a resistor of 1 kΩ/100W. If the voltage of the power supply is no higher
than 460 V, you can also use an incandescent lamp of 100W. If an incandescent lamp is used, it may
go off or the light may become very weak.
Power supply
380V
–
480V
VFD
R
S
T
U
V
W
Resistor 1 K
Ω
/100 W
Resistor 1 K
Ω
/100 W
Resistor 1 K
Ω
/100 W
Fig 8.2 Charging circuit example of driving devices of 460 V
8.4.2 Electrolytic capacitor replacement
Read the safety precautions carefully and follow the instructions to perform
operations. Otherwise, physical injuries or damage to the device may be
caused.
The electrolytic capacitor of a VFD must be replaced if it has been used for more than 35,000 hours.
For details about the replacement, contact the local INVT office.