Goodrive350-UL Series VFD
Basic operation instructions
-94-
Set value
Function
Description
motor)
6
Output voltage
0–1.5 times of rated voltage of VFD
7
Output power
0–Two times of rated power
8
Set torque value
0–Two times of rated current of motor
9
Output torque
0–Two times of rated current of motor
10
AI1 input value
0–10V/0–20mA
11
AI2 input value
-10V–10V
12
AI3 input value
0–10V/0–20mA
13
Input value of high-speed
pulse HDIA
0.00–50.00kHz
14
Set value 1 of Modbus
communication
-1000–1000, 1000 corresponds to 100.0%
15
Set value 2 of Modbus
communication
-1000–1000, 1000 corresponds to 100.0%
16
Set value 1 of
PROFIBUS\CANopen
communication
-1000–1000, 1000 corresponds to 100.0%
17
Set value 2 of
PROFIBUS\CANopen
communication
-1000–1000, 1000 corresponds to 100.0%
18
Set value 1 of Ethernet
communication
-1000–1000, 1000 corresponds to 100.0%
19
Set value 2 of Ethernet
communication
-1000–1000, 1000 corresponds to 100.0%
20
Input value of high-speed
pulse HDIB
0.00–50.00kHz
21
Reserved variable
22
Torque current (bipolar, 100%
corresponds to 10V)
0–Two times of rated current of motor
23
Exciting current (100%
corresponds to 10V)
0–One times of rated current of motor
24
Set frequency (bipolar)
0–Max. output frequency
25
Ramps reference frequency
(bipolar)
0–Max. output frequency
26
Running speed (bipolar)
0–Max. output frequency
27
Set value 2 of
EtherCAT/PROFINET
-1000–1000, 1000 corresponds to
100.0%
Содержание GD350-004G-2-UL
Страница 1: ...Goodrive350 UL Series High performance Multi function VFD ...
Страница 366: ...6 6 0 0 1 0 0 6 0 6 201911 V1 1 ...