Goodrive350-UL Series VFD
Function parameter list
-200-
Function
code
Name
Detailed parameter description
Default
value
Modi
fy
P13.06
Pulse current
setting
This parameter is used to set the pulse current
threshold when the initial magnetic pole position is
detected in the pulse mode. The value is a
percentage in relative to the rated current of the
motor.
Setting range: 0.0–300.0% (of the rated voltage of
the motor)
100.0%
◎
P13.07
Reserved
variables
0.0–400.0
0.0
○
P13.08
Control
parameter 1
0–0xFFFF
0
○
P13.09
Control
parameter 2
This parameter is used to set the frequency
threshold for enabling the counter-electromotive
force phase-locked loop in SVC 0. When the running
frequency is lower than the value of this parameter,
the phase-locked loop is disabled; and when the
running frequency is higher than that, the
phase-locked loop is enabled.
Setting range: 0–655.35
2.00
○
P13.10
Reserved
variables
0.0–359.9
0.0
○
P13.11
Maladjustment
detection time
This parameter is used to adjust the responsiveness
of anti-maladjustment function. If the load inertia is
large, increase the value of this parameter properly,
however, the responsiveness may slow down
accordingly.
Setting range: 0.0–10.0s
0.5s
○
P13.12
High-frequency
compensation
coefficient of
synchronous
motor
This parameter is valid when the motor speed
exceeds the rated speed. If motor oscillation
occurred, adjust this parameter properly.
Setting range: 0.0–100.0%
0.0
○
P13.13–
P13.19
Reserved
variables
0–65535
0
○
P14 group Serial communication function
P14.00
Local
communication
address
Setting range: 1–247
When the master is writing frames, and the slave
communication address is set to 0, it is the broadcast
1
○