-172-
Function
code
Name
Detailed parameter description
Default
value
Modi
fy
Tens: Reserved
P07.03
Running
command
channel
switch-over
sequence of
QUICK key
When P07.02=6, set the switch-over sequence of
running command channel.
0: keypad control→terminal control→
communication control
1: keypad control←→terminal control
2: keypad control←→communication control
3: terminal control←→communication control
0
○
P07.04
Stop function
selection of
STOP/RST key
Validness selection of stop function of STOP/RST.
For fault reset, STOP/RST is valid under any
situation.
0: valid only for panel control only
1: valid for both panel and terminal control
2: valid for both panel and communication control
3: valid for all control modes
0
○
P07.05–
P07.07
Reserved variables
/
/
P07.08
Frequency
display
coefficient
0.01–10.00
Display frequency=running frequency× P07.08
1.00
○
P07.09
Speed display
coefficient
0.1–999.9%
Mechanical speed=120×display running
frequency×P07.09/number of motor pole pairs
100.0%
○
P07.10
Linear speed
display
coefficient
0.1–999.9%
Linear speed=mechanical speed×P07.10
1.0%
○
P07.11
Temperature of
rectifier bridge
module
-20.0–120.0°C
/
●
P07.12
Temperature of
VFD module
-20.0–120.0°C
/
●
P07.13
Software version
of control board
1.00–655.35
/
●
P07.14
Accumulated
running time
0–65535h
/
●
P07.15
High bit of VFD
power
consumption
Display the power consumption of the VFD.
VFD power consumption=P07.15×1000+P07.16
Setting range of P07.15: 0–65535 kWh (×1000)
/
●