Goodrive350-UL Series VFD
Basic operation instructions
-74-
Function
code
Name
Detailed parameter description
Default
value
5: Multi-step (the same as above)
6: Modbus communication (the same as above)
7: PROFIBUS /CANopen/ DeviceNet
communication (the same as above)
8: Ethernet communication (the same as above)
9: Pulse frequency HDIB (the same as above)
10: EtherCAT/PROFINET communication
11: PLC
12: Reserved
Note:
Source 1-11, 100% relative to the max.
frequency
P03.15
Source of upper
limit frequency
setting of reverse
rotation in torque
control
0: Keypad (P03.17)
1: AI1 (100% corresponds to max. frequency)
2: AI2 (the same as above)
3: AI3 (the same as above)
4: Pulse frequency HDIA (the same as above)
5: Multi-step (the same as above)
6: Modbus communication (the same as above)
7: PROFIBUS /CANopen/ DeviceNet
communication (the same as above)
8: Ethernet communication (the same as above)
9: Pulse frequency HDIB (the same as above)
10: EtherCAT/PROFINET communication
11: PLC
12: Reserved
Note:
Source 1-11, 100% relative to the max.
frequency
0
P03.16
Keypad limit value
of upper limit
frequency of
forward rotation in
torque control
0.00Hz–P00.03 (Max. output frequency)
60.00 Hz
P03.17
Keypad limit value
of upper limit
frequency of
reverse rotation in
torque control
0.00Hz–P00.03 (Max. output frequency)
60.00 Hz
P03.18
Source of upper
limit setting of the
0: Keypad (P03.20)
1: AI1 (100% relative to three times of motor
0