Operation Manual of INVT CHS100 AC Servo Drive 6 Detailed parameter description
76
Function
code
Name
Unit
Range
Default
Mode
Pb.15
Speed detect filter time
256
μ
s 0~6000 0
P.S
This parameter is used to set the time constant of the speed detect filter.
Function
code
Name
Unit
Range
Default
Mode
Pb.16
Gain switching
selection
- 0~1 1 P.S
In the case of parameter Pb.17=0, i.e. at the manual gain switching mode, this
parameter can be used to select the manner of gain switching when the gain switching
terminal (PLC) signal is ON:
0: Speed loop gain switching
Realize the switching between PI regulation and P regulation of speed loop. The
corresponding relationships between the terminal status and the speed loop regulator
are:
PLC
Speed loop regulator
0 PI
regulation
1 P
regulation
0
:
OFF (the terminal is disconnected with COM-);
1
:
ON (the terminal is connected with COM-).
1: Switching the 1st gain to the 2nd
Realize the switching between the 1st gain and the 2nd gain. The corresponding
relationships between the terminal status and the 1st gain, the 2nd gain are:
PLC
Gain
0 1st
gain
1 2nd
gain
0:OFF (the terminal is disconnected with COM-);
1:ON (the terminal is connected with COM-).
The 1st gain and the 2nd gain include not only the proportional parameters but also the
integral parameters. Specifically are:
1st gain
2nd gain
1st position gain (Pb.01)
2nd position gain (Pb.06)
1st speed gain (Pb.04)
2nd speed gain (Pb.07)