Operation Manual of INVT CHS100 AC Servo Drive 5 Running and operation
48
zero speed and, after that, the motor is in a locked state.
When the servo enabling terminal (SON) signal is set to OFF, the servo
motor will stop. You can select the stopping method through setting
parameter Pc.52. See description of Pc.52 for details. This process will not
cause regenerative braking.
When an fault alarm occurs, the servo motor will stop. You can select the
stopping method of the servo motor when an alarm occurs through setting
parameter Pc.52. See description of Pc.52 for details. This process will not
cause regenerative braking.
When the zero speed clamp terminal (ZRS) signal is set to ON, the servo
motor will stop. In the position mode and torque mode, the servo motor will
stop immediately. In the speed mode, you can set parameter Pc.09 to
select whether the servo motor stops immediately or decelerates to stop
according to the settings of parameter Pc.01 and Pc.03. After stop the
servo is in a locked state. This stop process may cause regenerative
braking. If a braking overload fault alarm occurs, please install an external
braking resistor.
If the travel limit terminal signal is valid (parameter PA.16=1), and the travel
limit terminal (PSL/RVL) signal is set to OFF, the servo motor will
immediately decelerate to a stop and get into a locked state. After it stops
running, if a reverse running command is valid, the motor can run in
reverse direction.
If the emergency stop terminal signal is valid (parameter PA.17=1), and the
emergency stop terminal (EMG) signal is set to OFF, the servo motor will
coast to stop.