Operation Manual of INVT CHS100 AC Servo Drive 6 Detailed parameter description
63
Fig. 6-3 Schematic diagram of position/torque mode switching
6: Factory reserved mode. Setting by the user is prohibited.
Function
code
Name
Unit
Range
Default
Mode
PA.02
Default monitored
parameters
- 0~26 0 P.S.T
This parameter is used to set the parameters which can be monitored while
powering-on of the system:
0: Motor rotation speed;
1: Lower 5 digits of feedback pulse accumulation;
2: Higher 5 digits of feedback pulse accumulation;
3: Lower 5 digits of command pulse accumulation;
4: Higher 5 digits of command pulse accumulation;
5: Retention pulse
6: Analog speed command voltage;
7: Analog torque command voltage;
8: Main circuit power bus voltage;
9: Control circuit power bus voltage;
10: Effective value of current output current;
11: Current torque;
12: Drive module temperature;
13: Average load rate;
14: Position of the rotor relative to Z pulse;
15: Inertia ratio of load;
16: Third latest fault alarm code;
17: Second latest fault alarm code;
Position mode
Torque mode
Position mode
Zero speed
threshold (set
with PC.05)
Motor speed
Mode switching
signal (MCH)