This address (P330E) is used to set the Contact ID code that a Keypad Fire
“
4&6
”
alarm will transmit.
P330E Keypad Fire Alarm Contact ID Code -
3 Digit Number (Default = 110)
MEDICAL ALARM CONTACT ID CODE
This address (P331E) is used to set the Contact ID code that a Keypad Medical
“
7&9
”
alarm will transmit.
P331E Keypad Medical Alarm Contact ID Code -
3 Digit Number (Default = 100)
PROGRAMMING DIALER 4 + 2 REPORTING CODES
The dialer is capable of reporting most events in 4+2 format to a monitoring station. There are various 4+2 formats
(see telephone mode options on page 40).
The 4+2 format consists of a 4 character account code, plus a 2 character event code. The account & event codes
can be any combination of the values 1234567890BCDEF (see programming chart on page 32). If a value of
“
00
”
is
programmed into any 4+2 address (or the
“
Exclude
”
key is entered at a selected 4+2 address) then no report will be
generated for that event.
ZONE ALARM 4 + 2 REPORTING CODE
This block of addresses (P511E - P518E) are used to set the 4 + 2 code that a Zone will transmit in an alarm.
P511E Zone # 1 4 + 2 Code -
2 Digit Number (Default = 01)
P512E Zone # 2 4 + 2 Code -
2 Digit Number (Default = 02)
P513E Zone # 3 4 + 2 Code -
2 Digit Number (Default = 03)
P514E Zone # 4 4 + 2 Code -
2 Digit Number (Default = 04)
P515E Zone # 5 4 + 2 Code -
2 Digit Number (Default = 05)
P516E Zone # 6 4 + 2 Code -
2 Digit Number (Default = 06)
P517E Zone # 7 4 + 2 Code -
2 Digit Number (Default = 07)
P518E Zone # 8 4 + 2 Code -
2 Digit Number (Default = 08)
ZONE ALARM 4 + 2 RESTORE CODE
This block of addresses (P521E - P528E) are used to set the 4 + 2 code that a Zone will transmit when it is restored
following an alarm.
P521E Zone # 1 4 + 2 Code -
2 Digit Number (Default = 11)
P522E Zone # 2 4 + 2 Code -
2 Digit Number (Default = 12)
P523E Zone # 3 4 + 2 Code -
2 Digit Number (Default = 13)
P524E Zone # 4 4 + 2 Code -
2 Digit Number (Default = 14)
P525E Zone # 5 4 + 2 Code -
2 Digit Number (Default = 15)
P526E Zone # 6 4 + 2 Code -
2 Digit Number (Default = 16)
P527E Zone # 7 4 + 2 Code -
2 Digit Number (Default = 17)
P528E Zone # 8 4 + 2 Code -
2 Digit Number (Default = 18)
ZONE EXCLUDED 4 + 2 CODE
This block of addresses (P581E - P588E) are used to set the 4 + 2 code that a Zone will transmit if it is manually or
automatically excluded at the time of Arming.
P581E Zone # 1 Excluded 4 + 2 Code -
2 Digit Number (Default = 21)
P582E Zone # 2 Excluded 4 + 2 Code -
2 Digit Number (Default = 22)
P583E Zone # 3 Excluded 4 + 2 Code -
2 Digit Number (Default = 23)
P584E Zone # 4 Excluded 4 + 2 Code -
2 Digit Number (Default = 24)
P585E Zone # 5 Excluded 4 + 2 Code -
2 Digit Number (Default = 25)
P586E Zone # 6 Excluded 4 + 2 Code -
2 Digit Number (Default = 26)
P587E Zone # 7 Excluded 4 + 2 Code -
2 Digit Number (Default = 27)
P588E Zone # 8 Excluded 4 + 2 Code -
2 Digit Number (Default = 28)
ZONE EXCLUDE RESTORE 4 + 2 CODE
This block of addresses (P591E - P598E) are used to set the 4 + 2 code that a Zone will transmit if a manual or
automatic exclusion has been restored.
P591E Zone # 1 Exclude Restore 4 + 2 Code -
2 Digit Number (Default = 31)
P592E Zone # 2 Exclude Restore 4 + 2 Code -
2 Digit Number (Default = 32)