used for zones 4 & 8. Zone doubling is assigned on a zone-by-zone basis. Each input can be
configured as two zones (Type 3 drawing on page 5 ) without tamper monitoring or two zones
(Type 4 drawing on page 5 ) with tamper monitoring. To use the Type 3 mode for zones 1 & 5
you must turn LED#1 Off and LED#5 On. To use Type 4 mode for zones 1 & 5 you must turn
LED#1 On and LED#5 On. The same applies to the other zone inputs. Refer to the table on
Page 5 for more details.
PROGRAMMING ZONE OPTIONS
PROGRAMMING ZONE OPTIONS
–
P129E
,
P131E-P150E
This block of addresses (P129E - P150E) are used to select the desired functions for Zones 1-8
P131E Partition
“
A
”
Zones
Zones 1-8. (Default = All 8 zones)
This option allows programming of which zones will be assigned to Partition A. If a zone is in Both A & B then it
becomes common to both Areas.
P132E Partition
“
B
”
Zones
Zones 1-8. (Default = No zones)
This option allows programming of which zones will be assigned to Partition B. If a zone is in Both A & B then it
becomes common to both Areas.
P133E Zone is NC or NO
Zones 1-8. (Default =Led Off, All Zones NC, Normally Closed)
This option only applies if an input has been doubled e.g. by turning on option #5 at P130E the high zone (Zone 5)
is now turned on for that input. In this example, the panel is looking to see separate normally closed relay contacts
across the low (4K7) and high (8K2) resistors to seal each input. By turning the LED on for zone 1 at this address,
the panel is now looking for a Normally Open (NO) contact on the low zone (4K7).
P134E Radio Zone Input
Zones 1-8. (Default = No zones)
This option allows programming of which zones will be radio zones. If a zone is a radio zone, the panel ignores
the state of the hardwired input for that zone). If the zone input has been set to Zone doubling, the tampers are
still active even if both the low & high zones are set for Radio operation.
P135E Manually excludable Zone
Zones 1-8. (Default = All 8 zones)
This option allows programming of which zones can be manually excluded prior to Arming. If a zone has this
option turned off, then that zone cannot be excluded manually). Zones are excluded during the disarm state and
normal zones which are excluded become re-included once the alarm has been set then unset. 24 hour zones,
however remain excluded until manually re-included again. Every time the alarm is set or unset with zones
excluded, the keypad will respond with a long beep instead of the normal 3 short beeps to indicate that excludes
are present. When excluding zones, the READY\EXCL & PROGRAM LED
’
s are on to indicate that you have
entered exclude mode. After excluding zones the READY\EXCL led will flash when all zones are sealed to
indicate that zones are excluded.
P136E Auto-excludable Zone
Zones 1-8. (Default = All 8 zones)
This option allows programming of which zones can be automatically excluded at the end of the exit delay if
unsealed at that time. If a zone has this option turned off, then that zone will not auto-exclude and will go into
alarm if not sealed.
P137E Handover Zone
Zones 1-8. (Default = No zones)
This option allows programming of which zones will be handover zones. If a zone is a handover zone then it
’
s
entry delay time will apply provided a non-handover zone is triggered before the handover zone. If no other entry
delays are active when the handover zone is triggered, the zone will activate immediately.
P138E Two Trigger Zone
Zones 1-8. (Default = No zones)
This option allows programming of which zones will require two triggers before they activate. To cause an
activation a two trigger zone must alarm twice within the 2 trigger time period, P229E, or 2 two trigger zones can
alarm once each within the two trigger time period before the alarm is generated. If a two trigger zone is unsealed
and remains unsealed for a period longer than the two trigger time period, an alarm will also be generated.
P139E Monitor Mode Zone
Zones 1-8. (Default = Zone 1)
This option allows programming of which zones can be assigned as Monitor Mode Zones. Only zones
programmed at this address will be active when monitor mode is armed.
P129E 24 Hour Fire Zone
Zones 1-8. (Default = No zones)
This option allows a zone to be programmed as a 24 hour fire zone. If programmed as a fire zone, when the zone
causes an alarm if will flash any outputs it is programmed to operate at a rate set by the pulse timer (P221-228E).