164
Table 78. Hale SAM System Level SCR Table – CONTINUED
SYMPTOM
CAUSE
REMEDY
TWISTER SIGNAL LOST- OPERATE
WITH SCREEN
SAM communication with
the Twister control has
been lost.
Confirm Twister is operational.
Confirm MatrIIX Pressure Governor is
operational.
Wire Harness Discon-
nected/Damaged.
Check wiring continuity.
Equipment Failure
R&R failed Twister. See paragraph
4.4.5 (page 57).
R&R failed MatrIIX Pressure Gover-
nor. See paragraph 4.8.1 (page 92).
WARNING LOW FOAM TANK
(Foam Tank Level Has Reached The
Low Limit)
Associated Foam Concen-
trate Tank Is Empty
Fill the correct foam concentrate
tank. (Foam A and/or Foam B)
Foam Level Transducer
Requires Calibration
Refer to Intelli-Tank Level 40 (ITL-40)
Operation Manual (P/N 118253)
Foam Level Transducer
Failure
Refer to Intelli-Tank Level 40 (ITL-40)
Operation Manual (P/N 118253)
SmartFOAM Display
Failure
Refer to FSG-MNL-00158 (Smart-
FOAM manual).
SmartCAFS Display
Failure
Refer to FSG-MNL-00157 (CAFS
manual).
SAM Pump Controller
Failure
R&R failed SAM Pump Controller.
See paragraph 4.4.2 (page 53).
SAM Control Center
Failure
R&R failed SAM Control Center. See
WARNING LOW TANK WATER
SAM Reports Water Tank
Level Incorrectly Or ONLY
At Low Limit
Check ITL-40 harness connections.
Water Tank Level Trans-
ducer Requires Calibra-
tion
Refer to Intelli-Tank Level 40 (ITL-40)
Operation Manual (P/N 118253)
Water Tank Level Trans-
ducer Failure
Refer to Intelli-Tank Level 40 (ITL-40)
Operation Manual (P/N 118253)
WATER LEVEL SIGNAL LOST- FILL WA-
TER TANK MANUALLY
ITL-40 Lost Power Or CAN
Communication
Check harness power connections
and circuit breakers. See para-
graph 4.3.5 (page 48) and sec-
tion 4.10.6 (page 115).
Check harness Green CAN bus con-
nections. Refer to FSG-PL-01503/
FSG-PL-01504 and industry standard
Deutsch connector practices.
Check harness Green CAN bus re-
sistance. See paragraph 4.16.3
(page 170).
Check ITL-40 harness connections.
Equipment Failure
Refer to Intelli-Tank Level 40 (ITL-40)
Operation Manual (P/N 118253)
Содержание Hale Sam
Страница 2: ......
Страница 37: ...17 Figure 14 SAM Blue CAN Buss Architecture With Three SAM Control Centers Diagram...
Страница 38: ...18 Figure 15 SAM Green CAN Buss Architecture With Three SAM Control Centers Diagram...
Страница 39: ...19 Figure 16 SAM Red CAN Buss Architecture With Three SAM Control Centers Diagram...
Страница 40: ...20 Figure 17 SAM System Drain And Pneumatic Diagram...
Страница 41: ...21 Figure 18 SAM Speaks Diagram...
Страница 42: ......
Страница 58: ...38 THIS PAGE INTENTIONALLY BLANK...
Страница 62: ...42 THIS PAGE INTENTIONALLY BLANK...
Страница 192: ...172 THIS PAGE INTENTIONALLY BLANK...
Страница 206: ...186 THIS PAGE INTENTIONALLY BLANK...
Страница 220: ...200 THIS PAGE INTENTIONALLY BLANK...