The SAM discharge flow calibration requires each discharge be calibrated individually (only one
open discharge at one time) using an external calibrated Pitot gauge (or a calibrated flowmeter)
to determine the actual water flow. This procedure does NOT include setup for the calibrated Pi-
tot or flowmeter.
NOTES
The flow reading are always displayed in m
3
/hr (the J1939 standard unit).
An OEM/Technician password is required to access the screens to perform this proce-
dure. Contact the AHJ for applicable OEM/Technician information.
Perform the following to calibrate the valve position sensor for the selected discharge valve.
A.
Close all discharge valves.
B.
On SAM Control Center Home screen, touch System Options icon (touch and hold
icon if required).
C.
When Enter Password screen is displayed, enter OEM/ Technician password as
follows.
Connect USB key to USB dongle (rear of SAM Control Center).
Sequentially, touch password digits.
Touch ENTER button.
D.
On Display Menu screen, touch Calibration tab. (Refer to FSG-MNL-00211.)
E.
Touch FLOWMETER CALIBRATION button.
CALIBRATE VALVE FLOW screen appears (Figure 147).
Figure 147. Calibrate Valve Flow Screen
Содержание Hale Sam
Страница 2: ......
Страница 37: ...17 Figure 14 SAM Blue CAN Buss Architecture With Three SAM Control Centers Diagram...
Страница 38: ...18 Figure 15 SAM Green CAN Buss Architecture With Three SAM Control Centers Diagram...
Страница 39: ...19 Figure 16 SAM Red CAN Buss Architecture With Three SAM Control Centers Diagram...
Страница 40: ...20 Figure 17 SAM System Drain And Pneumatic Diagram...
Страница 41: ...21 Figure 18 SAM Speaks Diagram...
Страница 42: ......
Страница 58: ...38 THIS PAGE INTENTIONALLY BLANK...
Страница 62: ...42 THIS PAGE INTENTIONALLY BLANK...
Страница 192: ...172 THIS PAGE INTENTIONALLY BLANK...
Страница 206: ...186 THIS PAGE INTENTIONALLY BLANK...
Страница 220: ...200 THIS PAGE INTENTIONALLY BLANK...