138
4.12.3.4
How To Change/Set Low Intake Alert Trigger Point
The low intake alert trigger point is set from the Pump Controller, Governor Menu, page 4 screen
(see Figure 157) by setting the suction pressure governor enable pressure (PSI). Perform the fol-
lowing to change or set the low intake alert trigger point for SAM.
A.
On SAM Pump Controller (Figure 28, page 35), display SAM Pump Controller
Menu screen (see paragraph 2.6.1.2, SAM Pump Controller Password Screen Ac-
cess, page 35).
B.
Touch Governor Settings button. Governor Menu screen (Figure 113) is dis-
played.
C.
On Governor Menu screen, touch Page Down button (lower left-hand side of
screen) until Page 4 is displayed (highlighted) in upper right-hand corner of
screen.
D.
Touch Suction Pressure Governor Enable pressure (PSI) row (see Figure 113).
Figure 113. Suction Pressure Governor Enable Row Selected
E.
Touch wrench and gears button (lower right-hand side of screen).
F.
On SPG User Set Point screen (Figure 114), set New Value as follows.
Touch desired value (use number buttons on right-hand side of screen).
Touch ENTER button. (Touch CLEAR ALL or BACK SPACE button to delete all text box
data or delete only last data entry.)
Figure 114. SPG User Set Point Screen
Содержание Hale Sam
Страница 2: ......
Страница 37: ...17 Figure 14 SAM Blue CAN Buss Architecture With Three SAM Control Centers Diagram...
Страница 38: ...18 Figure 15 SAM Green CAN Buss Architecture With Three SAM Control Centers Diagram...
Страница 39: ...19 Figure 16 SAM Red CAN Buss Architecture With Three SAM Control Centers Diagram...
Страница 40: ...20 Figure 17 SAM System Drain And Pneumatic Diagram...
Страница 41: ...21 Figure 18 SAM Speaks Diagram...
Страница 42: ......
Страница 58: ...38 THIS PAGE INTENTIONALLY BLANK...
Страница 62: ...42 THIS PAGE INTENTIONALLY BLANK...
Страница 192: ...172 THIS PAGE INTENTIONALLY BLANK...
Страница 206: ...186 THIS PAGE INTENTIONALLY BLANK...
Страница 220: ...200 THIS PAGE INTENTIONALLY BLANK...