27.08.2018
123 / 136
EVO S -
Installation and Servicing
Line
No.
Programming
Access
Default value
Customer setting
2331
Output basic stage
S
S 50:
S 70:
S 95:
S 115:
S 135:
12
17
20
24
28
2334
Output at pump speed min
S
0 %
2335
Output at pump speed max
S
0 %
2441
Fan speed heating max
S
S 50:
S 70:
S 95:
S 115:
S 135:
7250
5480
6450
6950
6350
2442
Fan speed full charging max
S
S 50:
S 70:
S 95:
S 115:
S 135:
7250
5480
6450
6950
6350
2444
Fan speed DHW max
S
S 50:
S 70:
S 95:
S 115:
S 135:
7250
5480
6450
6950
6350
2454
Switching diff on HCs
S
3 °C
2455
Switching diff off min HCs
S
3 °C
2456
Switching diff off max HCs
S
6 °C
2457
Settling time HCs
S
20 min
2460
Switching diff on DHW
S
3 °C
2461
Switching diff off min DHW
S
3 °C
2462
Switching diff off max DHW
S
6 °C
2463
Settling time DHW
S
20 min
2470
Delay heat req special op
C
0 s
2503
Parameter
S
6 s
2630
Auto deaeration procedure
S
Off
2655
ON time deaeration
S
10 s
2656
OFF time deaeration
S
5 s
2657
Number of repetitions
S
3
2662
Deaeration time heat circuit
S
10 min
2663
Deaeration time DHW
S
5 min
Cascade
3510
Lead strategy
S
Late on, late off
3511
Output band min
S
30 %
3512
Output band max
S
90 %
3530
Release integral source seq
S
300 °Cmin
3531
Reset integral source seq
S
100 °Cmin
3532
Restart lock
S
300 s
3533
Switch on delay
S
5 min
3534
Forced time basic stage
S
60 s
3540
Auto source seq ch'over
S
500 h
3541
Auto source seq exclusion
S
none
3544
Leading source
S
source 1
3560
Return setpoint min
S
8 °C
3562
Return influence consumers
S
On
DHW storage tank
5020
Flow setpoint boost
S
16 °C
5021
Transfer boost
S
8 °C