EVO S -
Installation and Servicing
Settings on the Rubis
Adjust the outlet temperature set point on the Rubis to 58°C.
Summary of the rules for the adjustment of the set points for the DHW
Set point of the consuming circuit (low limit) = set point of the outlet T° of the Rubis +5°C
Set point of the DHW on the boiler = set point of the outlet T° of the Rubis -2°C
Over-value of the boiler outlet temperature when the DHW is restarted = 13°C
Process description
The consuming circuit keeps the temperature of the tank at 63°C. In this case, the set point of the
boiler = the set point of the consuming circuit (63°C).
If the sensor inside the tank detects a temperature = the set point of the DHW (56°C) -5°C=51°C,
the DHW cycle starts. The output temperature of the boiler is then = the set point of the DHW
(56°C) + over-value (13°C) = 69°C.
The DHW cycle stops when the sensor inside the tank reaches the DHW set point temperature
(56°C). The boiler then returns to the set point of the consuming circuit (63°).
• Activate the DHW mode
F. ELECTRICAL AND HYDRAULIC VALIDATION
•
Inputs/outputs test
menu
Check the outputs
Alarm relay
Relay test
(7700)
Relay output QX1
Tank pump Q15
Relay test
(7700)
Relay output QX3
Reset the outputs
Relay test
(7700)
No test
Check the sensor values
B3 DHW sensor
DHW temp B3/B38
(7750)
in °C
Check the status of contact H1
Contact state H1
(7841)
Closed if the shunt
is in place
• Configuration
menu
Check the hydraulic diagram
Check no. heat source 1
(6212)
13
Check no. heat source 2
(6213)
0
Check no. storage tank
(6215)
4
Check no. heating circuits
(6217)
0
Diagram: VF22
page 4 / 5
Line No. Value
• Configuration
menu
Save the sensors
Save sensors
(6200)
Yes (switches back
to no automatically)