98 / 136
00RNO0333-B (U0625869)
EVO S -
Installation and Servicing
Diagram: VF11
page 4 / 9
D. SPECIFIC START-UP PROCEDURE
"
"
Make the accessories' electrical connections.
"
"
Start up the boiler only.
"
"
Carry out the adjustments below.
On boiler No. 1: master
Line No. Value
• Configuration
menu
Boiler pump supplied by IDEAL
No adjustments necessary
Boiler pump supplied by the customer
(all-or-nothing control)
Relay output QX3
(5892) Boiler pump Q1
•
Time and date
menu
Set the time
Hours / minutes
(1)
HH.MM
Set the date
Day / month
(2)
DD.MM
Set the year
Year
(3)
YYYY
• Configuration
menu
Start up heating circuit 1
Heating circuit 1
(5710)
On
Start up heating circuit 2
Heating circuit 2
(5715)
On
Configure the alarm output
Relay output QX1
(5890)
Alarm output K10
Configure DHW pump Q3
Relay output QX2
(5891)
DHW ctrl elem Q3
Configure the cascade cylinder outlet
sensor B10
Sensor input BX2
(5931)
Common flow
sensor B10
Configure the extension modules
Function extension module 1
(6020)
Heat circuit 1
Function extension module 2
(6021)
Heat circuit 2
•
Configure as master of the cascade:
LPB network
menu
Appliance number
Device address
(6600)
1
Segment number
Segment address
(6601)
0
Adjust the bus supply
Bus power supply function
(6604)
Automatically
IMPORTANT:
Configure the switches on the AGU 2.550 extension modules.
Содержание EVO S 50