27.08.2018
119 / 136
EVO S -
Installation and Servicing
Line
No.
Programming
Access
Default value
Customer setting
726
Heating curve adaptation
S
Off
730
Summer/winter heating limit
E
19 °C
732
24-hour heating limit
S
--- °C
740
Flow temp setpoint min
C
8 °C
741
Flow temp setpoint max
E
80 °C
742
Flow temp setpoint room stat
E
65 °C
746
Delay heat request
C
0 s
750
Room influence
S
20 %
760
Room temp limitation
S
1 °C
761
Heating limit room controller
S
--- %
770
Boost heating
S
--- °C
780
Quick setback
S
Down to reduced setpoint
790
Optimum start control max
S
00:00
791
Optimum stop control max
S
00:00
800
Reduced setp increase start
S
--- °C
801
Reduced setp increase end
S
-15 °C
809
Continuous pump operation
S
No
820
Overtemp prot pump circuit
S
On
830
Mixing valve boost
S
3 °C
832
Actuator type
S
3-position
833
TOR Switching differential
S
2 °C
834
Actuator running time
S
120 s
835
Mixing valve Xp
S
32 °C
836
Mixing valve Tn
S
120 s
850
Floor curing function
C
Off
851
Floor curing setp manually
C
25 °C
855
Floor curing setp current
E
0 °C
856
Floor curing day current
E
0
861
Excess heat draw
S
Always
870
With buffer
S
No
872
With prim contr/system pump
S
No
881
Starting speed
S
100 %
882
Pump speed min
S
100 %
883
Pump speed max
S
100 %
888
Curve readj at 50% speed
S
33 %
889
Filter time const speed ctrl
S
5 min
890
Flow setp readj speed ctrl
S
Yes
898
Operating level changeover
S
Reduced
900
Optg mode changeover
S
Protection
Heating circuit 2
1010
Comfort setpoint
E
20 °C
1012
Reduced setpoint
E
18 °C
1014
Frost protection setpoint
E
10 °C
1016
Comfort setpoint max
S
35 °C
1020
Heating curve slope
E
1,5
1021
Heating curve displacement
S
0 °C
1026
Heating curve adaptation
S
Off
1030
Summer/winter heating limit
E
19 °C
1032
24-hour heating limit
S
--- °C
Содержание EVO S 50
Страница 2: ......
Страница 106: ...106 136 00RNO0333 B U0625869 EVO S Installation and Servicing...
Страница 135: ...27 08 2018 135 136 EVO S Installation and Servicing...