27.08.2018
91 / 136
EVO S -
Installation and Servicing
Diagram : VF10
page 4 / 7
Line No. Value
•
Time and date
menu
Set the time
Hours / minutes
(1)
HH.MM
Set the date
Day / month
(2)
DD.MM
Set the year
Year
(3)
YYYY
• Configuration
menu
Configure the cascade cylinder outlet sensor
B10
Sensor input BX2
(5931)
Common flow sensor
B10
For a request via 0...10V input
Configure the H1 input
Function input H1
(5950)
Consumer request
VK1 10V
Voltage value 1 H1
(5953)
0.0
Function value 1 H1
(5954)
0
Voltage value 2 H1
(5955)
10.0
Function value 2 H1
(5956)
1000 (for equivalence
10 V = 100 °C)
For a request via LPB
Check that the secondary regulatory is defined on an LPB segment other
than 0 (reserved for the generators)
In all cases (LPB network menu)
Configure the boiler as master the of the
cascade:
Device address
(6600)
1
Segment address
(6601)
0
Bus power supply function
(6604)
Automatically
Clock mode
(6640)
Master (or
slave with
remote setting if the
PLC is the master
clock)
To display the faults from other modules on
the console of the module you are adjusting
Display system messages
(6610)
Yes
If you want an alarm report on this module
(output K10 (QX1)) containing all the faults
from all the modules
Syst messages alarm relay
(6611)
Yes
Save the sensors
Save sensors
(6200)
Yes (switches back to
no automatically)