Installation and Servicing
E. SPECIFIC START-UP PROCEDURE
Make the accessories' electrical connections.
"
"
Start up the boiler only.
"
"
Carry out the adjustments below.
On EVO S boiler:
Line No. Value
• Time and date
menu
Set the time
Hours / minutes
(1)
HH.MM
Set the date
Day / month
(2)
DD.MM
Set the year
Year
(3)
YYYY
• Configuration
menu
Start up heating circuit 1
Heating circuit 1
(5710)
On
Start up heating circuit 2
Heating circuit 2
(5715)
On
Configure the alarme report
Relay output QX1
(5890)
Alarm output K10
Configure DHW pump
Relay output QX2
(5891)
DHW ctrl elem Q3
If the
boiler pump is supplied by
customer
Relay output QX
3
(5892)
Boiler pump Q1
Configure the extension modules
Function extension module 1
(6020)
Heat circuit 1
Function extension module 2
(6021)
Heat circuit 2
• LPB network
menu
Device number
Device address
(6600)
1
Segment number
Segment address
(6601)
0
Configure the bus supply
Bus power supply function
(6604)
Automatically
Set the clock program
Clock mode
(6640)
Master
• Heating circuit 1 / 2
Adjust the comfort setting
Comfort setpoint
(710/1010) - - -
Adjust the curve slope
Heating curve slope
(720/1020) - - -
IMPORTANT:
Configure the switches on the AGU 2.550 extension modules.
Diagram: VF4
page 4 / 8