27.08.2018
59 / 136
EVO S -
Installation and Servicing
Diagram: VF3
page 6 / 7
G. CONFIGURATION OPTIMISATION
Heating circuit optimisation
Line No.
Value
•
Heating circuit 1 / 2 / 3
menu
Adjust the reduced setting
Reduced setpoint
(712/1012/1312)
- - -
•
Heating circuit 2 / 3
menu
ECO function for automatic
summer / winter switch (see
NAVISTEM B3000 manual)
Function activated by default
Summer/winter heating limit
(1030/1330)
19 °C
Daily ECO function for
automatic comfort / reduced
switch according to the
difference
between
the
set point and the outdoor
temperature (see NAVISTEM
B3000 manual).
Function not activated by
default
24-hour heating limit
(1032/1332)
-3 °C
•
Heating circuit 1 / 2 / 3 timer programme
menu
Preselection
Preselection
(500/520/540)
- - -
Adjust the timer programming
On / off phases
(501...506)
(521...526)
(541...546)
- - -
•
Heating circuit 1 / 2 / 3 holiday
menu
Preselection
Preselection
(641/651/661)
- - -
Adjust the timer programming
On / off phases
(642...-643)
(652-653)
(662-663)
- - -
• Switch the heating regime to automatic
Auto
DHW optimisation:
•
DHW tank
menu
Adjust the over value
Flow setpoint boost
(5020)
16 °C