EVO S -
Installation and Servicing
figure 12 - EVO S 70 to S 95 settings
R1
U0561579-#
R2
- If the setting is adjusted at minimum power, go
back to maximum power Qmax and recheck the
CO
2
value. Repeat the operation until both values
comply with the table below.
- Return to the standard operating mode.
After changing the type of gas:
- Check the sealing of the gas line.
- Stick the G31 label provided in place of the
original label (G20).
Door open
pre-setting
Checking the door
closed settings
Model Gas
Pre-adjustment of the gas flow
adjusting screw R1
CO
2
Pmax
Indicative
CO
2
Pmin
CO
2
Pmax
Indicative
CO
2
Pmin
S 50
G20
- -
9,0 - 9,2
8,6 - 8,8
9,1 - 9,3
8,7 - 8,9
G31
Screw R1 3 turns 3/4
Screw R2 1/4 turn
10,2 - 10,4 9,8 - 10,0 10,3 - 10,5 9,9 - 10,1
S 70
G20
- -
9,0 - 9,2
8,5 - 8,7
9,1 - 9,3
8,7 - 8,9
G31
Screw R1 1/4 turn
Screw R2 1/4 turn
10,2 - 10,4 9,7 - 9,9 10,3 - 10,5 9,9 - 10,1
S 95
G20
- -
9,0 - 9,2
8,5 - 8,7
9,1 - 9,3
8,7 - 8,9
G31
Don't touch R1
Unscrew R2 1/8 turn
10,2 - 10,4 9,7 - 9,9 10,3 - 10,5 9,9 - 10,1