76 / 136
00RNO0333-B (U0625869)
EVO S -
Installation and Servicing
Diagram: VF22
page 3 / 5
E. SPECIFIC START-UP PROCEDURE
"
"
Make the accessories' electrical connections.
"
"
Start up the boiler only.
"
"
Make the following settings:
Line No. Value
•
Time and date
menu
Set the time
Hours / minutes
(1) HH.MM
Set the date
Day / month
(2) DD.MM
Set the year
Year
(3) YYYY
• Configuration
menu
Configure the alarm output
Relay output QX1
(5890)
Alarm output K10
Configure the tank pump
Relay output QX3
(5892)
Consumer circuit
pump 1 Q15
Define a low limit
Function input H1
(5950)
Consumer request
VK1
Position a shunt on H1
OU
reverse the
contact direction
Contact type
(5951)
Normally-closed
contact (NC)
For the DHW to be effective, an
activator must be defined, even if it is
not connected
Relay output QX2
(5891)
DHW ctrl elem Q3
•
Consumer circuit 1
menu
Set the output setting to be taken into
account if the Consumer circuit is
requested
Flow temp setp cons request
(1859) 60 °C (depends on
the Rubis setting)
Remove pump stoppage on DHW
priority (OEM setting)
DHW priority
(1874) No
•
Domestic hot water menu
Adjust the comfort setting
Nominal setpoint
(1610) 3°C less than the
Rubis set point
Adjust the DHW release mode
Release
(1620) 24h/day
Remove the DHW priority
Charging priority
(1630) Without
• DHW tank
menu
Adjust the over value
Flow setpoint boost
(5020)
13 °C