27.08.2018
73 / 136
EVO S -
Installation and Servicing
Line No. Value
Check the sensor values
External sensor B9
Outside temp B9
(7730)
in °C
•
Configuration
menu
Check the hydraulic diagram
Check no. heat source 1
(6212)
14
Check no. heat source 2
(6213)
0
Check no. storage tank
(6215)
0
Check no. heating circuits
(6217)
2
Diagrams: VF20, VF21, VF21bis
page 5 / 5
G. CONFIGURATION OPTIMISATION
Heating circuit optimisation:
•
Heating circuit 1
menu
Adjust the reduced setting
Reduced setpoint
(712)
- - -
•
Heating circuit 1 timer programme
menu
Preselection
Preselection
(500)
- - -
Adjust the timer programming
On / off phases
(501...506)
- - -
•
Heating circuit 1 holiday
menu
Preselection
Preselection
(641)
- - -
Adjust the timer programming
On / off phases
(642...-643)
- - -
• Switch the heating regime to automatic
Auto
Maintenance optimisation
A maintenance message may be generated that does not set the boiler to fault. This maintenance
message may be displayed after the following 3 counters have expired:
•
Time since last maintenance (or commissioning): set parameter 7044 to 12 months.
•
Operating hours of the burner (parameter 7040).
•
Number of starts (parameter 7042)
These last 2 parameters are dependent on the boiler's hydraulic installation. We recommend
using at least parameter 7044 for annual maintenance.
IMPORTANT:
In diagram VF21, it is IMPERATIVE to programme the same ranges
on the unit heater for the optimisation to work.
Содержание EVO S 50
Страница 2: ......
Страница 106: ...106 136 00RNO0333 B U0625869 EVO S Installation and Servicing...
Страница 135: ...27 08 2018 135 136 EVO S Installation and Servicing...