27.08.2018
57 / 136
EVO S -
Installation and Servicing
Diagram: VF3
page 4 / 7
Line No. Value
Configure the boiler pump or alarm report
IDEAL supply
Configure the alarm output
Relay output QX1
(5890)
Alarm output K10
Customer supply (all-or-nothing control)
Configure the output
(no more
alarm outputs available)
Relay output QX1
(5890)
Boiler pump Q1
Configure DHW pump
Relay output QX2
(5891)
DHW ctrl elem Q3
Configure the direct circuit pump Q2
Relay output QX3
(5892)
Heat circuit pump
HC1 Q2
Configure the extension modules
Function extension module 1
(6020)
Heat circuit 2
Function extension module 2
(6021)
Heat circuit 3
• Heating circuit 1 / 2 / 3
menu
For each circuit:
Adjust the Comfort setpoint
Comfort setpoint
(710/1010/1310) - - -
Adjust the curve slope
Heating curve slope
(720/1020/1320) - - -
Adjust the min. flow temperature for
heating circuit 1
Flow temp setpoint min
(740)
60°C (adjust
according to the
lower limit)
Removal of the over-value
Mixing valve boost
(830)
0 °C
•
Switch the heating regime to permanent comfort
• Domestic hot water
menu
Adjust the Comfort setpoint
Nominal setpoint
(1610) - - -
• Activate the DHW mode
• Configuration
menu
Save the sensors
Save sensors
(6200)
Yes (switches back
to no automatically)