60
CRX-POSTX-DIN
DIN Rail PostX IP Reporting Module
Installation Manual | June 2017
The Dial Attempts option must be programmed. Refer to the section
Contact ID | Settings
in the the
Protege GX Operator Reference Manual (227-1500-000).
DACT communication channel check-in time is not to exceed 24 hrs.
Trouble Zone Service Test Report
The Test Report Time must be programmed. Refer to the section
Controllers | Configuration
in the
Protege GX Operator Reference Manual (227-1500-000).
The Generate Input Restore on Test Input option must be enabled. Refer to the section
Controller |
Options
in the Protege GX Operator Reference Manual (227-1500-000).
The Test Report Time is Periodic option must be enabled. Refer to the section
Controller | Options
in
the Protege GX Operator Reference Manual (227-1500-000).
ArmorIP detects the reception of any invalid packet on the programmed port as a potential system
compromise attempt. Each compromise attempt sends a notification to the receiver, and logs a
Compromise Attempt event under the Live Panel Events.
The event is sent with the following details:
Account Code as defined in the Serial Receiver settings
Event Code 0x163
Group Code as defined in the Serial Receiver settings
Point Code as defined in the Serial Receiver settings
Refer to the section
Global Settings | Serial Receiver
in the ArmorIP Internet Monitoring Application User's
Manual (227-5500-000).
For UL and ULC installations the Central Station Receiving software must have the Contact ID details as
specified, programmed for the Compromise Attempt event.
If a flexible cord is used to connect to line voltage, strain relief must be provided for the cord inside the
enclosure or at the knockout.
The Power Supply is not intended to be mounted on the exterior of vault, safe, or stockroom.
UL294
The Models PRT-CTRL-DIN and PRT-RDM2-DIN are intended to be mounted within the enclosure (refer to
UL/ULC Installation Cabinet Options (see page 52)), installed inside the protected premise, and are UL 294
Listed for Attack Class I applications only
Exit devices and wiring must be installed within the protected area.
For the Models PRT-CTRL-DIN and PRT-RDM2-DIN, all RS485 and reader terminal connections must be
made using shielded grounded cable.
All readers must be connected with shielded, grounded cable.
A bell or visual indicator used as an arming acknowledgement signal must be listed to a UL security,
signaling or fire standard. If intended to be mounted outside, it must be rated for outdoor use.
Fail secure locking mechanism shall only be installed where allowed by the local authority having jurisdiction
(AHJ) and shall not impair the operation of panic hardware and emergency egress.
If fire resistance is required for door assembly, portal locking device(s) must be evaluated to UL10B or
UL10C.
Must be installed with UL 1034 listed electronic locks for UL installations.