CRX-POSTX-DIN
DIN Rail PostX IP Reporting Module
Installation Manual | June 2017
57
ETHERNET
ENCLOSURE
FIRE
SUPERVISORY
TROUBLE
FIRE ALARM PANEL
Z1
Z2
Z3
PRT-CTRL-DIN
COM STATUS / FB
MAINS SUPPLY
(120V AC)
AC
AC
CAN/ULC-S559
PRT-CTRL-DIN
ACTIVE COMMUNICATION
INTERNET
TELECOM
EQUIPMENT
24h Standby / Backup
Required for Telecom
Equipment
Note: All cables shall be protected within metal conduits.
Metal Conduit
* Fire zones shall be separated from burglar zones through area partitioning.
* Fire zones Z1-Z3 shall be used exclusively for fire monitoring and cannot be programmed to activate the bell output
* EOL resistor must be installed at the Fire Alarm Control Panel Output.
RELAY 1 or 2
Dry Contacts
Typical Zone Circuits
Value 1
Value 2
Monitored Status
1K
1K
Open, Close, Tamper, Short
6K8
2K2
Open, Close, Tamper, Short
10K
10K
Open, Close, Tamper, Short
2K2
2K2
Open, Close, Tamper, Short
4K7
2K2
Open, Close, Tamper, Short
4K7
4K7
Open, Close, Tamper, Short
+AUX-
Z1
COM
C
OM
Z2
Z3
Z4
N.C
Tamper
N.C Zone Contact
Value 2
Value 1
+
-
+
-
PRT-PSU-DIN or equivalent
ULC certified 12V DC Power Supply
12V DC
485
485
Lumex AC Power
Status Indicator
(SSI-LXH312GD-150)
+ -
C
NC
NC
C
12VDC
AC
FAIL
BATT
FAIL
1K5
* The AC FAIL output on the Power Supply
MUST
be programmed to follow the AC Trouble Input as follows:
AC FAIL = OPEN on fail