Installation Manual | June 2017
ETHERNET
ENCLOSURE
FIRE
SUPERVISORY
TROUBLE
FIRE ALARM PANEL
Z1
Z2
Z3
PRT-CTRL-DIN
COM STATUS / FB
MAINS SUPPLY
(120V AC)
AC
AC
CAN/ULC-S559
PRT-CTRL-DIN
PASSIVE COMMUNICATION
INTERNET
TELECOM
EQUIPMENT
24h Standby / Backup
Required for Telecom
Equipment
Note: All cables shall be protected within metal conduits.
Metal Conduit
* Fire zones shall be separated from burglar zones through area partitioning.
* Fire zones Z1-Z3 shall be used exclusively for fire monitoring and cannot be programmed to activate the bell output
* EOL resistor must be installed at the Fire Alarm Control Panel Output.
RELAY 1 or 2
Dry Contacts
Typical Zone Circuits
Value 1
Value 2
Monitored Status
1K
1K
Open, Close, Tamper, Short
6K8
2K2
Open, Close, Tamper, Short
10K
10K
Open, Close, Tamper, Short
2K2
2K2
Open, Close, Tamper, Short
4K7
2K2
Open, Close, Tamper, Short
4K7
4K7
Open, Close, Tamper, Short
+AUX-
Z1
COM
C
OM
Z2
Z3
Z4
N.C
Tamper
N.C Zone Contact
Value 2
Value 1
+
-
+
-
PRT-PSU-DIN or equivalent
ULC certified 12V DC Power Supply
12V DC
485
485
Lumex AC Power
Status Indicator
(SSI-LXH312GD-150)
+ -
C
NC
NC
C
12VDC
AC
FAIL
BATT
FAIL
1K5
* The AC FAIL output on the Power Supply
MUST
be programmed to follow the AC Trouble Input as follows:
AC FAIL = OPEN on fail
DIALER
PSTN
TELECOM
EQUIPMENT
Fire Zone Inputs and Outputs
Fire Zone inputs must be programmed as follow:
FACP Fire Alarm Signal zone type must be programmed as Fire
Supervisory Trouble Signal zone type must be programmed as 24 Hr Silent
Trouble Signal zone type must be programmed as 24 Hr Silent
Please refer to the section
Inputs | Areas and Input Types
in the Protege GX Operator Reference Manual
(227-1500-000)
All fire zone inputs must be placed into an area and this area must be armed. Please refer to the section
Inputs | Areas and Input Types
in the Protege GX Operator Reference Manual (227-1500-000)
COM Status
FACP system with a COM STATUS input must have this input connected to one of the dry relay contacts of
the Relay1 or Relay2 outputs of the PRT-CTRL-DIN and the selected output must be programmed as the
Report OK PGM in the Contact ID Service.
Note: Any available dry relay contact on the PRT-CTRL-DIN or PRT-PX8-DIN may be used for the FACP
system, provided the selected output is programmed as the Report OK PGM.
Please refer to section
Contact ID | Settings
in the Protege GX Operator Reference Manual (227-1500-000)
Fire zones Z1-Z3 shall be used exclusively for fire monitoring and cannot be programmed to activate the bell
output.