56
CRX-POSTX-DIN
DIN Rail PostX IP Reporting Module
Installation Manual | June 2017
The Report IP and Contact ID services must be programmed and enabled within the Protege System. The
following options are required:
The Contact ID Reporting Service must be enabled and the Service Mode must be configured to start
with the operating system.
Refer to the section
Contact ID
in the Protege GX Operator Reference Manual (227-1500-000).
The Report IP Service must be enabled as the primary communication channel, the Service Mode
must be configured to start with the operating system, and the Reporting Protocol must be set to
ArmorIP.
Refer to the section
Report IP
in the Protege GX Operator Reference Manual (227-1500-000).
The Trouble Area must be armed. Refer to the section
Trouble Inputs | Areas and Input Types
in the
Protege GX Operator Reference Manual (227-1500-000).
In the ArmorIP Internet Monitoring Software the Poll Time must be set to 40 seconds and the Grace Time
must be set to 20 seconds. Refer to the section
Poll/Grace Time
in the ArmorIP Internet Monitoring
Application User Manual (227-5500-000).
Central Station Signal Receiver
The maximum number of signal transmitting units connected to any transmission channel shall conform to
the manufacturer's recommendations. The ArmorIP Receiver supports up to 10000 simultaneous
connections.
Refer to the section
Internet Connections Requirements
in the ArmorIP Receiver Installation Manual
(227-5510-000) for further details.
Number of attempts
In the event of unsuccessful communication, a digital alarm communicator transmitter shall make a
minimum of 5 and a maximum of 10 attempts. Where the maximum number of attempts to complete the
sequence is reached, an indication of the failure shall be made at the premises.
In the Protege System, the reporting service selected as Contact ID must have the number of attempts
programmed to 5 attempts. The Dialing Attempts option must be programmed. Refer to the section
Contact ID | Settings
in theProtege GX Operator Reference Manual (227-1500-000).
Check-In Time
DACT communication channel check-in time is not to exceed 24 hrs.
Trouble Input Service Test Report
The Test Report Time must be programmed. Refer to the section
Controllers | Configuration
in the
Protege GX Operator Reference Manual (227-1500-000).
The Generate Input Restore on Test Input option must be enabled. Refer to the section
Controller |
Options
in the Protege GX Operator Reference Manual (227-1500-000).
The Test Report Time is Periodic option must be enabled. Refer to the section
Controller | Options
in
the Protege GX Operator Reference Manual (227-1500-000).
Ethernet Connections
All Ethernet network connections shall be installed within the same room as the equipment.
Power Supply Mains Power Connection
If a flexible cord is used to connect to line voltage, strain relief must be provided for the cord inside the
enclosure or at the knockout.
The Power Supply is not intended to be mounted on the exterior of vault, safe, or stockroom.
Arming Signal
A bell or visual indicator used as an arming acknowledgement signal must be listed to a ULC security,
signaling or fire standard. If intended to be mounted outside, it must be rated for outdoor use.
Keypad Wiring
The RS-485 connection to the keypad must be wired such that the shorts and other faults on the RS-485
line connection of the keypad will not cause the controller to malfunction.
Fire Zones
Fire zones shall be separated from burglar zones through area partitioning.
NOTE: Any available dry relay contact on the PRT-CTRL-DIN or PRT-PX8-DIN may be used for the FACP
system, provided the selected output is programmed as the Report OK PGM.