Attention:
If your system is powered on and performing I/O operations, go to
the management GUI and follow the fix procedures. Performing the replacement
actions without the assistance of the fix procedures can result in loss of data or
access to data.
Attention:
A powered-on enclosure must not have a power supply removed for
more than five minutes because the cooling does not function correctly with an
empty slot. Ensure that you have read and understood all these instructions and
have the replacement available, and unpacked, before you remove the existing
power supply.
Even though many of these procedures are hot-swappable, these procedures are
intended to be used only when your system is not up and running and performing
I/O operations. Unless your system is offline, go to the management GUI and
follow the fix procedures.
Be careful when you are replacing the hardware components that are located in the
back of the system that you do not inadvertently disturb or remove any cables that
you are not instructed to remove.
Attention:
In some instances, it might not be advisable to remove a power supply
unit when a system is performing I/O. For example, the charge in the backup
battery might not be sufficient enough within the partner power-supply unit to
continue operations without causing a loss of access to the data. Wait until the
partner battery is 100% charged before replacing the power supply unit.
Ensure that you are aware of the procedures for handling static-sensitive devices
before you replace the power supply.
A replacement power supply unit is not shipped with a battery; therefore, transfer
the battery from the existing power supply unit to the replacement unit. To
transfer a battery, go to “Replacing a battery in a power supply unit” on page 93.
To replace the power supply, perform the following steps:
1.
Read the safety information to which “Preparing to remove and replace parts”
on page 79 refers.
2.
Examine the Identify LED that is lit on the front of the enclosure to identify
the correct enclosure.
3.
Turn off the power to the power supply units using the switches at the back
of the units.
4.
Disconnect the cable retention bracket and the power cord from the power
supply that you are replacing.
5.
Remove the power supply unit. Record the orientation of the power supply
unit. Power supply unit 1 is top side up, and power supply unit 2 is inverted.
a.
Depress the black locking catch from the side with the colored sticker as
shown in Figure 29 on page 87.
86
Storwize V7000: Troubleshooting, Recovery, and Maintenance Guide
|
|
|
Содержание Storwize V7000
Страница 1: ...IBM Storwize V7000 Version 6 3 0 Troubleshooting Recovery and Maintenance Guide GC27 2291 02...
Страница 6: ...vi Storwize V7000 Troubleshooting Recovery and Maintenance Guide...
Страница 8: ...viii Storwize V7000 Troubleshooting Recovery and Maintenance Guide...
Страница 10: ...x Storwize V7000 Troubleshooting Recovery and Maintenance Guide...
Страница 34: ...18 Storwize V7000 Troubleshooting Recovery and Maintenance Guide...
Страница 42: ...26 Storwize V7000 Troubleshooting Recovery and Maintenance Guide...
Страница 80: ...64 Storwize V7000 Troubleshooting Recovery and Maintenance Guide...
Страница 128: ...112 Storwize V7000 Troubleshooting Recovery and Maintenance Guide...
Страница 156: ...140 Storwize V7000 Troubleshooting Recovery and Maintenance Guide...
Страница 166: ...150 Storwize V7000 Troubleshooting Recovery and Maintenance Guide...
Страница 171: ......
Страница 172: ...Printed in USA GC27 2291 02...