Before You Begin
Verify that the rack can meet the drawer model operating
parameters, as detailed in Table 12.
Table 12. PC Server 325 Operating Specifications
Size
– Depth: 465 mm (18.3 in.)
– Height: 216 mm (8.5 in.)
– Width: 482 mm (19.0 in.)
Weight
Typical server as shipped: 17 kg
(37.5 lb)
Environment
Air temperature:
– Server on: 10° to 35° C
(50° to 95° F)
Altitude: 0 to 914 m (3000 ft.)
– Server on: 10° to 32° C
(50° to 90° F)
Altitude: 914 m (3000 ft.) to
2133 m (7000 ft.)
– Server off: 10° to 43° C
(50° to 110° F)
Maximum Altitude: 2133 m
(7000 ft.)
Humidity:
– Server on: 8% to 80%
– Server off: 8% to 80%
Maximum altitude: 2133 m
(7000 ft)
Electrical Input
Sine-wave input (50 to 60 Hz) is
required
Input voltage:
– Low range:
- Minimum: 90 V ac
- Maximum: 137 V ac
– High range:
- Minimum: 180 V ac
- Maximum: 265 V ac
– Input kilovolt-amperes (kVA)
approximately:
- Minimum configuration
as shipped: 0.08 kVA
- Maximum configuration:
0.52 kVA
Total Power Available for Drives
Nominal Operating Current
allowed:
– +5 V dc line: 5.3 A
– +12 V dc line: 5.0 A
Heat Output
Approximate heat output in
British Thermal Units (Btu) per
hour:
– Minimum configuration:
350 Btu (102 watts)
– Maximum configuration:
860 Btu (251 watts)
230
PC Server 325 User's Handbook
Содержание PC Server 325
Страница 1: ...PC Server 325 User s Handbook IBM...
Страница 6: ...vi PC Server 325 User s Handbook...
Страница 10: ...Laser Compliance Statement x PC Server 325 User s Handbook...
Страница 136: ...Updating the Server Configuration 122 PC Server 325 User s Handbook...
Страница 212: ...Resolving Configuration Conflicts 198 PC Server 325 User s Handbook...
Страница 238: ...Installed Device Records 224 PC Server 325 User s Handbook...
Страница 287: ......
Страница 288: ...IBM Part Number 76H8831 Printed in U S A September 1996 76H8831...