Exchanging the Fan Tray
Attention: The fan tray
is not hot pluggable on 2216s that have a Release 1 system card (PN number
75H5081 or 85H7916). You must shut down the 2216 completely before replacing the fan tray. If the fan
tray is removed, or if two or more fans fail, the box may shut down.
The fan tray is hot pluggable on 2216s that do not have the Release 1 system card (PN number 75H5081
or 85H7916); however, you must install the new tray within 3 minutes of removing the defective tray to
prevent overheating the IBM 2216.
1
Loosen the two thumbscrews that secure the fan tray and remove the fan tray.
2
Slide the new fan tray in until the tabs on the back of the fan tray are in the slots. This aligns the
connectors with the plugs.
3
When the fan tray is flush with the box, tighten the two thumbscrews.
Chapter 2. Removal and Replacement Procedures
2-13
Содержание Nways 2216
Страница 1: ...2216 Nways Multiaccess Connector ÉÂÔ Service and Maintenance Manual SY27 0350 02 ...
Страница 2: ......
Страница 3: ...2216 Nways Multiaccess Connector ÉÂÔ Service and Maintenance Manual SY27 0350 02 ...
Страница 8: ...vi 2216 Maintenance Manual ...
Страница 10: ...Common Tasks and the IBM 2216 Library viii 2216 Maintenance Manual ...
Страница 45: ...6 Remove the adapter from its location Chapter 2 Removal and Replacement Procedures 2 15 ...
Страница 60: ...3 6 2216 Maintenance Manual ...
Страница 84: ...4 24 2216 Maintenance Manual ...
Страница 104: ...A 2 2216 Maintenance Manual ...
Страница 106: ...Assembly 1 Final Assembly 2216 Model 400 B 2 2216 Maintenance Manual ...
Страница 110: ...B 6 2216 Maintenance Manual ...
Страница 114: ...1 2 3 4 5 6 7 8 9 10 Figure C 1 Power Cord Plugs by Country C 4 2216 Maintenance Manual ...
Страница 138: ...F 12 2216 Maintenance Manual ...
Страница 150: ...UWAGA Całkowicie wypełnione urządzenie IBM 2216 waży około 43 1 kg H 6 2216 Maintenance Manual ...
Страница 164: ......
Страница 167: ......