Preparing the rack enclosure:
In this section, you
will use the following parts:
Two slide bracket assemblies
Two slide rails (fitted to system unit)
One cable-management arm
Ten long screws (M6 by 16 mm)
Ten cage nuts
Installation template
Attention
To ensure cabinet stability, plan the installation of
servers in the rack enclosure starting from the bottom.
Note
This procedure requires two people.
To attach the mounting hardware to the rack
enclosure:
1. Mark the positions of the slide brackets on the
mounting rails on the rack enclosure.
a. Position the template on the front mounting rail
on the rack enclosure, aligning the holes.
Secure the template in place with tape.
b. Mark the holes for the slide brackets and cage
nuts. If you prefer, mark
all the cage nut
positions on the rack at this time.
c. Carefully remove the tape from the mounting
rails, and attach the template to the rear
mounting rails. Mark the locations for the slide
brackets and cage nuts.
Notes
1. You must align the slide brackets correctly,
or the installation cannot be completed.
2. The slide rails have four screws each to
allow for length adjustment.
2. Install the cage nuts in the marked positions as
shown.
3. Attach the slide rail to the left side of the rack
enclosure.
104
Netfinity Server HMM
Содержание 865951Y - Netfinity 5000 - 51Y
Страница 2: ......
Страница 8: ...vi Netfinity Server HMM...
Страница 12: ...Keyboards 172 Power cords 174 4 Netfinity Server HMM...
Страница 195: ...Related service information 187...
Страница 196: ...188 Netfinity Server HMM...
Страница 197: ...Related service information 189...
Страница 198: ...190 Netfinity Server HMM...
Страница 208: ...200 Netfinity Server HMM...
Страница 209: ...Related service information 201...
Страница 219: ......
Страница 220: ...IBM Part Number 10K2657 Printed in U S A S1 L 9837 4...