NO TICE
If the load of a single battery cabinet is less than or equal to 150 kW, you are
advised to set the I1 value of the battery circuit breaker to the MIN value shown
in the figure and use cables with a cross-sectional area of 120 mm
2
. If the load of
a single battery cabinet is greater than 150 kW, you are advised to use cables with
a cross-sectional area of 150 mm
2
.
Figure 4-46 Setting I1 to MIN for the battery circuit breaker
Procedure
Step 1 Install cables to the UPS.
Figure 4-47 Installing cables (UPS5000-H/S)
(1) Master SmartLi cabinet
SmartLi 2.0
User Manual
4 Installation