Table 10-4 Electrical specifications of a single cabinet
Item
8+8 scenario
(SmartLi-512V-80
AH-F-01-16/
SmartLi-512V-80
AH-S-01-16)
8+0 Scenario
(SmartLi-512V
-80AH-F-01-8/
SmartLi-512V-
80AH-S-01-8)
7+7 Scenario
(SmartLi-512V-80
AH-F-01-14/
SmartLi-512V-80
AH-S-01-14)
7+0 Scenario
(SmartLi-512V-80A
H-F-01-7/
SmartLi-512V-80AH
-S-01-7)
Rated voltage
512 V (3.2 V/cell)
448 V (3.2 V/cell)
Charge
voltage
544 V (3.4 V/cell)
476 V (3.4 V/cell)
Rated
capacity
80 Ah
40 Ah
80 Ah
40 Ah
Energy
40.96 kWh
20.48 kWh
35.84 kWh
17.92 kWh
Charge
current
≤ 80 A, 40 A by
default (The
actual charge
current depends
on the UPS charge
capability.)
≤ 40 A, 20 A by
default (The
actual charge
current
depends on the
UPS charge
capability.)
≤ 80 A, 40 A by
default (The
actual charge
current depends
on the UPS charge
capability.)
≤ 40 A, 20 A by
default (The actual
charge current
depends on the UPS
charge capability.)
Rated
discharge
current
500 A
250 A
500 A
250 A
Battery
neutral wire
connected
Supported
Battery
neutral wire
not connected
Supported
Parallel
system
A maximum of 15 cabinets can be connected in parallel.
Number of
battery
modules
16
8
14
7
SmartLi 2.0
User Manual
10 Technical Specifications
Issue 09 (2022-01-30)
Copyright © Huawei Technologies Co., Ltd.
157