Check Item
Expected Result
Troubleshooting
Battery
connection
reliability
check
(recommend
ed)
1. When battery strings are
powered off, check the
reliability of copper bars and
communications and
sampling terminals for each
battery module from positive
terminals (and neutral
terminals if any) to negative
terminals.
2. In copper bar check, use a
torque wrench to check the
tightening torque for each
battery screw. The torque
meets the requirements of
the battery manufacturer.
After checking that the
battery screws meet the
requirements, mark the
screws for later check.
1. Rectify any abnormal
connection.
2. If the fault persists,
contact technical support.
SmartLi 2.0
User Manual
7 Routine Maintenance
Issue 09 (2022-01-30)
Copyright © Huawei Technologies Co., Ltd.
132