Figure 9-19 Installing a fire-trace tube
(1) If the pipe holding device is slip-proof gloves, install the fire-trace tube using slip-proof
gloves.
3. Tighten the connection nut to 7 N·m using an adjustable torque wrench.
Step 7 Remove the valve positioning kit, open the valve, reinstall the positioning kit, and
secure it.
NO TICE
Slowly open the valve. To avoid unexpected blowout, do not quickly open the
valve.
Figure 9-20 Opening the valve
SmartLi 2.0
User Manual
9 Parts Replacement
Issue 09 (2022-01-30)
Copyright © Huawei Technologies Co., Ltd.
153