Paramete
r
Description
Configuration
Principle
Default Value
Requirem
ent
control
Enable or disable the
requirement control
for the master
device.
● When the
requirement
control is Enable,
the master device
synchronizes data
(the temperature
and humidity
control type and
set points of the
master device and
other parameters)
to the slave
device, and all the
smart cooling
products in the
group refer to the
mode delivered
by the master
device.
● When the
requirement
control is Disable,
the master device
does not
synchronize data
to the slave
device, and all the
smart cooling
products operate
based on their
own
requirements, not
referring to the
mode delivered
by the master
device.
The requirement
control function is
recommended for
the following
scenario: In one
teamwork, the
temperature and
humidity control
type and
temperature and
humidity set point of
units are the same,
and device heat
loads are distributed
evenly.
Disable
NetCol8000-A(050, 100) In-room Air Cooled Smart
Cooling Product
User Manual
5 ACC Introduction
Issue 12 (2020-10-28)
Copyright © Huawei Technologies Co., Ltd.
109